Features
- Intrinsically safe classification: (Ex ib) Gr2 C, T6.
- Direct interface with NAMUR two wire proximity switches.
- Failsafe operation.
- Sensor cable fault detection and indication.
- Low power sensor signal to DIN19234.
- SPDT relay outputs.
Specifications
Power Supply
AC:
Supply Voltage: 115, 230V ±15%
Isolation (sensor input to power supply): 2kV
Power Consumption: 3VA approximately
DC:
Supply Voltage: 24V ±15%
Isolation: No galvanic isolation
Power Consumption: 100mA
Sensor Input
Type: NAMUR (DIN 19234)
Quiescent Voltage: <8.2V DC
Short circuit current: <25mA
Max External Capacitance: <300nF (AC Supply), <700nF (DC Supply)
Max External Inductance: <2mH
Relay Options: SPST (PINS 1 & 3, NO), DPST (PINS 1 & 3 NO / PINS 11 & 9, NO)
Maximum Relay Current: 5A
Maximum Relay Voltage: 250V
Maximum Relay of the current and voltage: 100VA
Internal Fuse Rating: (AC Supply) 100mA, 250V