Description
Features
- Interfaces with industrial standard NAMUR sensors (inductive or capacitive).
- Low power sensor signal to DIN19234
- Programmable charge or discharge modes.
- Programmable single or double sensor selection.
- Independant indication of each sensor status.
- Separate cable fault indication for each sensor.
- Failsafe operation under cable fault conditions.
- Direct interface with solid state relay.
- Protected NPN output for direct interface with PLC’s or counters.
- 10A SPDT relay output.
- DC or AC power supply option.
Specifications
Power Supply
AC:
Supply Voltage: 12, 24, 115, 230, 400, 415, 525 ±15%
Isolation (sensor input to power supply): 2kV
Power consumption: 3VA, 6VA for 415, 525V (approx)
DC:
Supply Voltage: 10-30V, 48, 60, 110V ±15%
Isolation: No galvanic isolation
Power Consumption: 100mA (10-30V), 30mA for higher ranges.
Sensor Input
Type NAMUR (DIN19234)
Maximum Sensing Speed: 25Hz (When using relay output)
Short Circuit Current: 20mA DC
Open Circuit Voltage: 8.2V DC
Outputs (SP)
NPN Open Connector (9, 11)
Solid State Relay Drive (8, 9)
C/O (1, 3, 4)
If DP Contacts, no solid state O/P